CJ

FIREFIGHTING NOZZLE

The CJ firefighting nozzle series consists of water mist firefighting systems that, thanks to their integrated nozzles, finely atomize water droplets at an operating pressure of 100 bar for efficient flame suppression.

First, the mist of droplets absorbs a significant amount of thermal energy during evaporation, helping to counteract temperature increases. Then, the resulting water vapor alters the oxygen-to-fuel ratio, reducing combustion efficiency and hindering the fire. Finally, by absorbing a large portion of the flames’ radiant energy, the system minimizes the risk of surrounding materials reaching their ignition temperature.

AngleCode
Capacity (l/min) at different pressure values (bar)
5060708090100110120130140
150°CJX A050 B1XG
3.503.904.204.504.705.005.205.505.705.90
CJX A080 B1SG
5.706.206.707.207.608.008.408.89.109.50
CJX A100 B1SG
7.107.708.408.909.5010.010.511.011.411.8
CJX A140 B1XG
9.9010.811.712.513.314.014.715.316.016.6
CJX 1050 B1XG
3.503.904.204.504.705.005.205.505.705.90
CJX 1080 B1SG
5.706.206.707.207.608.008.408.89.109.50
CJX 1100 B1SG
7.107.708.408.909.5010.010.511.011.411.8
CJX 1140 B1SG
9.9010.811.712.513.314.014.715.316.016.6

CJ kod1

CJ kod2
Fire Fighting nozzle without bulb
Fire Fighting nozzle with bulb